3-Phase Active Front End Power Module
AFE 35kW – Scalable to 1MW total system power
Description
The AFE335KAC is a non-isolated fully integrated 3-phase active front end power module that is suitable for use as a bidirectional grid connected rectifier in systems for renewable energy, battery chargers, energy storage and general-purpose converters.
The AFE335KAC takes a 3-phase AC input voltage and converts it into a high voltage DC output. It will control the input power factor to a specified level and allows independent control of both active and reactive current or power. Furthermore, it offers a choice of different control modes including direct active/reactive power control, direct active/reactive current control and DC output voltage control.
If enabled, it supports bidirectional power flow with a seamless transition between delivery of power to and from the AC grid.
Grid-forming or backup mode of operation is also supported but requires an external load transfer switch to switch the load between on-grid and off-grid modes.
Multiple modules can be parallelled in a system to support power levels exceeding 1MW, while internal fusing on both power ports reduces the need for external components, which is particularly advantageous in those systems having many parallel modules.
Features
- 35kW Nominal DC Power
- Parallel Operation
- Low AC Current Harmonics
- Active & Reactive Power Control
- Regulates DC Output Voltage
- Direct Power or Current Control
- Bidirectional Power Flow
- Air Cooled
- CAN Interface for Control & Monitoring
- AC (Grid) & DC fuses built in
Block Diagram
Typical/Recommended Operating Conditions
Parameter
Grid Voltage (L-L), nominal
Grid Voltage (L-L), Operating range
Grid Current
Grid Frequency
Grid Voltage Phase Imbalance (Note 1)
DC Voltage Range
DC Current
Operating Temperature Range Ambient Full Power (Note 1)
AUX & CAN Power Supply Input Voltage
AUX & CAN Power Supply Input Current
Grid Power Factor (controllable via comm. interface)
Grid Current THD (at full power)
DC Voltage Accuracy (from setpoint)
Peak Efficiency
Idle Apparent Power (not connected to Grid)
Standby Active Power (connected to grid, power factor set to unity)
Standby Reactive Power (connected to grid, power factor set to unity)
Min
400
360
–
47
–
700
-46
-20
23
–
0.9 lagging
–
-0.5
–
–
–
–
Max
400
480
50
63
3
900
46
40
27
2.40
0.9 leading
5
0.5
98.2
1
50
100
Unit
Vrms
Vrms
Arms
Hz
%
Vdc
A
°C
V
A
–
%
%
%
VA
W
VAr
Protection Features
- DC voltage high
- AC voltage out of range
- High
- Low
- Phase imbalance
- No AC synchronization
- Operating temperature high
- Internal fault
Normative
Approvals
CE Approval Directives:
- 2014/30/EU (Electromagnetic Compatibility (EMC) Directive)
- 2014/35/EU (Low Voltage Directive)
- 2011/65/EU (RoHS Directive)
UL Approval upon request.
Safety
- IEC62477-1 (Safety requirements for power electronic converter systems and equipment)
- ul1741 (Upon request)
EMC
- IEC61000-6-2, immunity (industrial environments)
- IEC61000-6-3, emission (residential, commercial, and light-industrial environments)
For complete set of specifications, please request the datasheet below.